Four practical measurement methods of cable fault point

author:huining   add time:2016-01-12 09:41:24   browse:

打印本文             

A type of cable fault, and judgment

Both the high voltage cable or low voltage cables in construction, installation and operation in the process due to the frequent short circuit, overload, aging or damage due to insulation failure. Cable grounding fault is divided into three types, short-circuit and disconnection. Three core cable fault types are mainly the following aspects: a core or two core wire contact; two-phase short-circuit; three-phase core wire complete circuit; a core wire disconnection or multiphase disconnection.

For direct short circuit or disconnection fault with a multimeter direct measurement can judge for non direct short circuit and connecting the battery fault, megohm table telemetry between core line insulation resistance or cored wire insulation resistance to earth, the resistance is used to the fault type judges.

Two, search method of cable fault point

1, the acoustic measurement method

The so-called acoustic measurement method is searched according to the fault cable discharge sound, the method for high voltage cable insulation layer of flashover discharge is more effective. This method with the equipment of DC voltage test machine. The circuit connection as shown in Figure 1, where SYB is the high voltage test transformer, C high voltage capacitor, ZL high voltage silicon rectifier stack, R current limiting resistor, Q discharge ball gap, L cable.

When the capacitor C is charged to a voltage value, the ball gap of cable fault core wire discharge. In fault cable wire of insulating layer discharge produced "AIDS, AIDS, the spark of acoustic, again in the miscellaneous noise when the minimum, with the aid of the hearing aid or medical stethoscope and other audio equipment in your search. Find the pickup close to the ground, along the cable to move slowly, when heard "AIDS, AIDS, put electroacoustic largest, where is the point of failure. Use this method to Caution!, in the end and the end of the cable test equipment should be set up to monitor.

2, bridge method

DC resistance is measured by double bridge bridge cable core values, then the accurate measurement of actual length of cable, cable length and proportional relationship in accordance with the resistance of the fault point calculation. According to this method for the measurement of the method for cable core wire short circuit or short circuit point contact resistance less than 1 ohm fault judgment error is generally less than 3m, for the contact resistance of the fault point greater than 1 ohm fault, using high voltage burn through the method the resistance is reduced to less than 1 ohm. The measuring circuit is shown in Figure 2. First, the resistance R1 between core wire a and B is measured, then R1 = 2RX + R, where R is a phase resistance value of the a phase or B phase to the fault point, and R is the contact resistance of short contact point. Then on the other end of the cable to measure the a 'and B' between the DC resistance value R2, then R2 = 2R (X - L) + R, R (X - L) for the a 'and B' 'core line to the fault point of a phase resistance value. Finished measuring R1 and R2, and according to figure 3 shows circuit will b 'and C' 'short circuit, measured between B and C two-phase core line DC resistance value is 1 / 2 of the resistance of the resistance of the core line of each phase value, RL said. RL = RXR (LX), the contact resistance of the fault point value: R = R1R22RL. Therefore, the resistance value of the fault point on both sides can be expressed by the following formula: RX = (R - /2) R1, R (X - L) = (R - /2) R2. Rx, R (L x), RL three numerical determined, according to the proportion of formula can for fault location from the cable end of the distance X or (L x): x = (RX/RL) l (L - x) = (R (L x) /RL) l, type L is the total length of the cable.

When the bridge method is used to ensure the accuracy of the measurement, the bridge connecting line should be as short as possible, the diameter should be large enough, and the cable core wire connection to the use of compression or welding arm, the calculation process of small and medium-sized to all retain.

3, capacitive current measurement method

Cable in operation, between the core wire and core wire to ground there is a capacitance and the capacitance is uniformly distributed, the capacitance and the length of cable is linearly proportional to, the capacitance current determination method is based on the principle of determination, for the cable core wire disconnection fault determination is very accurate. The measuring circuit as shown in Figure 4, the use of equipment for 1 ~ 2kVA single phase voltage regulator, 0 ~ 30V, 0.5 AC voltage meter, a 0 ~ 100mA, 0.5 AC Ma Table 1.

Measurement steps:

(1) first in the first end of the cable to measure the capacitance of each line of the current (should maintain the voltage to maintain the same voltage) Ia, Ib, Ic value.

(2) at the end of the cable is measured per phase core wire capacitance current ia '', IB ', IC' value, to check the intact core wire and the wire core volume ratio, initially determine the approximate point break distance.

(3) according to the capacity calculation formula C = 1 / 2 pi Fu shows, in U voltage and frequency f constant C and I is proportional to, because the voltage frequency f (frequency) unchanged, when measured as long as the guarantee applied voltage is kept constant, capacitive current ratio as the ratio of capacitance. The length of the cable is L, the distance between the core and the line break point is Ia/Ic, then L/x = x, x = (Ic/Ia) L.

In the process of measurement, as long as the voltage is guaranteed, the current meter readings are accurate, the total length of the cable is accurate, and the measurement error is relatively small.

4, zero potential method

The zero potential method is also the potential comparison method, which adapts to the short cable core line to ground fault, the application of this method is simple and accurate measurement, does not require precision instruments and complex calculations, the wiring is shown in figure 5. The measuring principle is as follows: the cable fault core wire is parallel to the length of the equal length, and is equal to the power supply at both ends of the two parallel resistors when the E is pressed at both ends. At this point, the electric potential difference between any point on the resistance wire and the corresponding point on the other resistance wire is bound to be zero. Conversely, the potential difference for zero points must be corresponding points, because the microvolt meter negative ground, and cable fault point potential, so when microvoltmeter cathode in more conductive on mobile to showing the value of zero point and the point of failure and potential, namely fault point of the corresponding points.

Figure 5 K single-phase knife switch, E 6V battery 4 or 1 dry cell batteries, G DC microvoltmeter, the measurement procedure is as follows:

(1) first in B and C phase core wire connected to the battery e, in ground laying a root and the faulted cable length equal comparison s wire and the wire to with bare copper wire or bare wire, the section should be equal, not the middle joint.

(2) the microvolt meter anode grounding, anode is connected to a long soft wire. At the other end of the wire requirements in slide wire laying can fully contact.

(3) the knife blade switch K, the soft wire breakage in comparison to the wire sliding, when microvolt meter indication for zero position is the location of cable fault.


on aWith the application of general armoured cable
nextHow to prevent the transmission line


CONTACT

We always believe that the "user first, quality first" purpose and dedication to provide quality services for the majority of users

  • phone:0550-7561479
  • fax:0550-7562650
  • address:Anhui province Tianchang city Tongcheng town Qiaoba road No. 99

ScanningVisitMobile version

Scan two-dimensional code concerned about WeChat

popular keywords:
Anhui HuiNing Electric Instrument Group Co., Ltd.  皖ICP备05001032号-3